INSTALLATION OPERATION
AND SERVICE MANUAL
MICOFLAME SERIES 2
GAS FIRED COMMERCIAL COPPER TUBE BOILERS
FOR HYDRONIC HEATING
Models; MFH800, 1000, 1200, 1400, 1600, 1800, 2000
HOT WATER SUPPLY
Models; MFW800, 1000, 1200, 1400, 1600, 1800, 2000
H
HLW
WARNING: If the information in these instructions is not
followed exactly, a fire or explosion may result causing
property damage, personal injury or death
Do not store or use gasoline or other flammable
vapours and liquids in the vicinity of this or any other
appliance.
WHAT TO DO IF YOU SMELL GAS
o Do not try to light any appliance,
o Do not touch any electrical switch; do not use any
phone in your building,
o Immediately call your gas supplier from a
neighbour’s phone. Follow the gas supplier’s
instructions,
o If you cannot reach your gas supplier, call the fire
department.
Qualified installer, service agency or the gas supplier
must perform installation and service.
To the installer: After installation, these instructions must be
given to the end user or left on or near the heater.
To the End User: This booklet contains important information
about this heater. Retain for future reference.
CAMUS HYDRONICS LTD.
6226 Netherhart Road, Mississauga, Ontario, L5T 1B7
Vue de la page 0
1 2 3 4 5 6 ... 52 53

Résumé du contenu

Page 1 - AND SERVICE MANUAL

99-0053 Rev. 04 INSTALLATION OPERATION AND SERVICE MANUAL MICOFLAME SERIES 2 GAS FIRED COMMERCIAL COPPER TUBE BOILERS FOR HYDRONIC HEATING Mod

Page 2

6 When an existing boiler is removed from a common venting system, the common venting system is likely to be too large for proper venting of the appl

Page 3 - Table of Contents

7 8. While the boiler is operating, check for flue gas leaks and proper vent operation. Seal any flue gas leaks using appropriate gasket or se

Page 4

8 7.2 SIDEWALL VENTING When fitted with the factory supplied vent terminal, the MicoFlame series 2 can vent up to 60 equivalent feet. Elbows can r

Page 5 - 1 GENERAL INSTRUCTIONS

9 7.4 FILTER KIT A louvered rear panel is the standard air inlet configuration for the MicoFlame series 2. A filter kit is availa

Page 6 - 2 BOILER LOCATION

10 RELIEF VALVE (shipped loose) This appliance is supplied with a relief valve sized in accordance with ASME Boiler and Pressure Vessel Code, Section

Page 7 - 4 ELECTRICAL WIRING

11 9 FREEZE PROTECTION • Appliance installations are not recommended outdoors in areas where danger of freezing exists unless precautions are taken

Page 8 - Table 3: Burner Firing Rates

12 11 PIPING OF BOILER TO SYSTEM (FIG.5) Check all applicable local heating, plumbing and building safety codes before proceeding. Be sure to provid

Page 9 - 7 VENTING

13 If the boiler is installed above radiation level, it must be provided with a low water cutoff device at the time of boiler installation. (Availabl

Page 10

14 Figure 6 – Display, Appliance Temperature Controller and Indicating LED The Boiler Temperature Controller (BTC) for this appliance is a Camus 78

Page 11 - 7.1 OUTDOOR VENTING

15 KEY KEY DESCRIPTION Item The abbreviated name of the selected item will be displayed in the item field of the display. To view the next item, p

Page 13

16 13.2.1 MODE 1 & 2: SETPOINT OPERATION Mode 1 Intended for hydronic heating. The set-point for inlet water control is pre-set to 180°F and t

Page 14

17 13.2.2 MODE 1 & 2: SETPOINT OPERATION: VIEW DISPLAY From the Home display; 1) Press [ITEM] to view the following parameters: Display Parame

Page 15 - 9 FREEZE PROTECTION

18 13.2.3 MODE 1 & 2: SETPOINT OPERATION: ADJUST DISPLAY From the Home display; 1) Press simultaneously to view the following parameters:

Page 16

19 13.2.4 MODE 3: DHW SETPOINT OPERATION Mode 3 is intended for domestic water heating. The set-point for inlet water control is pre-set to 140°F a

Page 17

20 13.2.6 MODE 3: DHW SETPOINT OPERATION: ADJUST DISPLAY From the Home display; 1) Press simultaneously to view the following parameters: Displa

Page 18

21 13.2.7 MODE 4 & 5: OUTDOOR RESET OPERATION Mode 4 is intended for hydronic heating. The set-point for inlet water control is pre-set to 180°F

Page 19

22 13.2.8 MODE 4 & 5: OUTDOOR RESET OPERATION: VIEW DISPLAY From the Home display; 1) Press [ITEM] to view the following parameters: Display Pa

Page 20

23 13.2.9 MODE 4 & 5: OUTDOOR RESET OPERATION: ADJUST DISPLAY From the Home display; 1) Press simultaneously to view the following parameter

Page 21

24 Pump Delay Boiler post pump time after burner has shut off, in seconds. OFF, 0:20 to 9:55 min, On Default = 1:00 min Warm Weather Shutdown Temp

Page 22

25 13.2.11 MODE 7: EXTERNAL TARGET TEMPERATURE USING SYSTEM TEMPERATURE SENSOR The external input signal can be provided from a BMS, EMS or a Tekma

Page 23

Table of Contents INTRODUCTION ...

Page 24

26 13.2.12 MODE 6 & 7: EXTERNAL TARGET TEMPERATURE INPUT OPERATION: VIEW DISPLAY From the Home display; 1) Press [ITEM] to view the following pa

Page 25

27 13.2.13 MODE 6 & 7: EXTERNAL TARGET TEMPERATURE INPUT OPERATION: ADJUST DISPLAY From the Home display; 1) Press simultaneously to view th

Page 26

28 Display Parameter Name Parameter Description Parameter Range Minimum Modulation Selects the minimum modulation rate 0% to 50% Default = 0% Max

Page 27

29 4-20 mA Boiler Target 0-10V (dc)* Boiler Target 0 - - - (OFF) 0 - - - (OFF) 2 - - - (OFF) 1 50oF (10oC) 4 50oF (10oC) 2 68oF (20oC) 6 70oF

Page 28

30 • Adjustment procedure. a. Fully open bypass and outlet valves. b. With boiler running, read inlet temperature after 15 minutes. c. If the i

Page 30

32 18 PILOT AND MAIN BURNER FLAMES To maintain safe operation and the greatest efficiency of the boiler, check the main burner and p

Page 31

33 1. Shut off power and close main manual gas valve. • Allow burner to cool before removal. 2. Remove access cover screws. • Disconnect pilot

Page 32

34 18.2 PILOT BURNER Turn the pilot firing valve to off position and allow the boiler to try for ignition. Observe the spark making sure that it is

Page 33

35 19 OPERATION AND SERVICE OPERATION: Before operating the boiler, the entire system must be filled with water, purged of air and checked for

Page 34

20 LIGHTING INSTRUCTIONS ...

Page 35

36 8. Open the main manual and main firing valves to allow gas to reach the main burner. If the main burner fails to ignite, turn the firing valve of

Page 36 - 18.1 MAIN BURNER

37 22 TYPICAL GAS TRAIN Figure 11: Gas Train 23 ELECTRICAL DIAGRAMS Each MicoFlame series 2 boiler will be provided with its own wiring diagram

Page 39 - LIGHTING INSTRUCTIONS

40 Tekmar BTC-4PA Electrical Connections Tekmar BTC-4PA Terminal # Label Description 1 CD Unused 2 HtD Call for heat signal 3 Pr D Proo

Page 41 - ELECTRICAL DIAGRAMS

42 MicoFlame II Gas Train

Page 42

43 MicoFlame II 800 – 1000 Control Box

Page 43

44 25 MICO FLAME REPLACEMENT PARTS LIST MicoFlame II Model Size Item # Part Description 800 1000 1200 1400 1600 1800 2000 1 Combustio

Page 44

45 MicoFlame II Model Size Item # Part Description 800 1000 1200 1400 1600 1800 2000 19 Combustion Chamber Support - Centre N/A 14-4

Page 45

1 INTRODUCTION Camus Hydronics proudly introduces its MicoFlame series 2 of commercial water heaters / hydronic boilers. These gas-burn

Page 46 - MicoFlame II Gas Train

46 MicoFlame II Model Size Item # Part Description 800 1000 1200 1400 1600 1800 2000 39 Return Header 15-5005 40 Header Bar 15-4157

Page 47

47 MicoFlame II Model Size Item # Part Description 800 1000 1200 1400 1600 1800 2000 59 Ignitor Module (Continuous) S8610M3017 Ignitor

Page 48

48 WARRANTY GENERAL Camus Hydronics Limited (“Camus”), extends the following LIMITED WARRANTY to the owner of this appliance, provided that t

Page 49

CAMUS Hydronics is a manufacturer of replacement parts for most copper finned The CAMUS CERTIFIED! Seal assures you that Reliability, Effic

Page 50

2 2 BOILER LOCATION Install this boiler in a clean, dry location with adequate air supply and close to a good vent connection. Do not locate this b

Page 51 - LXR5010S128230

3 Table 2: Various Connection Sizes B' Dia. Venting* E' Dia. Model W' Water Connection Gas Connection Outdoor Condensing or

Page 52 - WARRANTY

4 5 STAGING OPERATION Staging of the MicoFlame series 2 is dependent on the number of burners supplied. Models 800 and 1000 are supplied with a si

Page 53

5 6 GAS SUPPLY AND PIPING This boiler is intended to operate at inlet gas pressures not exceeding ½ PSI (14“ W.C.). If higher press